NAME

       mge-shut, newmge-shut - Driver for SHUT Protocol UPS equipment

NOTE

       This  man  page  only  documents  the hardware-specific features of the
       mge-shut  driver.   For  information  about  the   core   driver,   see
       nutupsdrv(8).

SUPPORTED HARDWARE

       mge-shut  support  all  recent Eaton, MGE and Dell UPS models which use
       the SHUT (Serial HID UPS Transfer) protocol.

       Older MGE models, such as Pulsar ESV+, Pulsar EX and  Pulsar  ES+,  use
       the U-Talk protocol and should use the mge-utalk driver.

EXTRA ARGUMENTS

       This   driver   supports   the   following  optional  settings  in  the
       ups.conf(5):

       lowbatt=num
              Set the low battery  warning  threshold  at  which  shutdown  is
              initiated  by  upsmon(8).   The  factory default value is 30 (in
              percentage), and only be settable depending on the exact  model.

       offdelay=num
              Set  the timer before the UPS is turned off after the kill power
              command is sent (via the -k switch).  The default  value  is  20
              (in seconds), and MUST BE LOWER than ondelay.

       ondelay=num
              Set the timer for the UPS to switch on in case the power returns
              after the kill power command had been sent but before the actual
              switch  off. This ensures the machines connected to the UPS are,
              in all cases, rebooted after a power failure.  The default value
              is  3 (in 10 seconds units, which means 30 seconds), and MUST BE
              GREATER than offdelay.

       notification=num
              Set notification type to 1 (no), 2  (light)  or  3  (yes).   The
              default  value  is  3 (yes) because of some early Ellipse models
              which need it.

KNOWN ISSUES

   Pulsar Ellipse S: Repetitive stale status - Loss of communication
       Several users have reported "data stale"  errors  with  Pulsar  Ellipse
       equipment.   This  lasts  around  10 seconds and happens once every few
       hours.  This is due to the fact that the SHUT protocol is verbose,  and
       the driver sometimes does not handle all of it during the usual polling
       interval in upsd.  To solve this problem, change the value of MAXAGE to
       25  in  upsd.conf.   Also  add  "notification=3" in ups.conf (thanks to
       Julien Lesaint and Fabien).

AUTHOR

       Arnaud Quette <arnaud.quette@free.fr> or <arnaud.quette@mgeups.com>

       Philippe Marzouk <philm@users.sourceforge.net>

SEE ALSO

   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

       MGE      UPS       SYSTEMS       SHUT       protocol       information:
       http://random.networkupstools.org/protocols/mge/

                                Thu Nov 19 2009                    mge-shut(8)