Man Linux: Main Page and Category List

NAME

       upsmon - UPS monitor and shutdown controller

SYNOPSIS

       upsmon -h

       upsmon -c command

       upsmon [-D] [-p] [-u user]

DESCRIPTION

       upsmon is the client process that is responsible for the most important
       part of UPS monitoring - shutting down the system when the  power  goes
       out.   It  can  call  out  to  other  helper  programs for notification
       purposes during power events.

       upsmon can monitor multiple systems using a single process.  Every  UPS
       that  is defined in the upsmon.conf(5) configuration file is assigned a
       power value and a type (slave or master).

OPTIONS

       -h     Display the help message.

       -c command
              Send the command command to the existing upsmon process.   Valid
              commands are:

              fsd - shutdown all master UPSes (use with caution)

              stop - stop monitoring and exit

              reload   -   reread   upsmon.conf(5)  configuration  file.   See
              "reloading nuances" below if this doesn't work.

       -D     Raise the debugging level.  upsmon will run  in  the  foreground
              and  prints  information on stdout about the monitoring process.
              Use this multiple times for more details.

       -K     Test for the shutdown flag.  If it exists and contains the magic
              string  from  upsmon,  then  upsmon will exit with EXIT_SUCCESS.
              Any other condition will make upsmon exit with EXIT_FAILURE.

              You can test for a  successful  exit  from  upsmon  -K  in  your
              shutdown  scripts to know when to call upsdrvctl(8) to shut down
              the UPS.

       -p     Run privileged all the time.  Normally upsmon  will  split  into
              two processes.  The majority of the code runs as an unprivileged
              user, and only a tiny stub  runs  as  root.   This  switch  will
              disable  that  mode,  and  run  the  old "all root all the time"
              system.

              This is not the recommended mode, and you should  not  use  this
              unless you have a very good reason.

       -u user
              Set  the user for the unprivileged monitoring process.  This has
              no effect when using -p.

              The default user  is  set  at  configure  time  with  'configure
              --with-user=...'.    Typically   this  is  'nobody',  but  other
              distributions will probably have a specific 'nut' user for  this
              task.   If  your  notification scripts need to run as a specific
              user, set it here.

              You can also set  this  in  the  upsmon.conf(5)  file  with  the
              RUN_AS_USER directive.

UPS DEFINITIONS

       In  the  upsmon.conf(5), you must specify at least one UPS that will be
       monitored.  Use the MONITOR directive.

            MONITOR system powervalue username password type

       The   system   refers   to   a   upsd(8)   server,    in    the    form
       upsname[@hostname[:port]].   The default hostname is "localhost".  Some
       examples follow:

        - "su700@mybox" means a UPS called "su700" on a system called "mybox".
       This is the normal form.

        -  "fenton@bigbox:5678"  is  a  UPS called "fenton" on a system called
       "bigbox" which runs upsd(8) on port "5678".

       The powervalue refers to how many power supplies  on  this  system  are
       being driven this UPS.  This is typically set to 1, but see the section
       on power values below.

       The username  is  a  section  in  your  upsd.users(5)  file.   Whatever
       password  you  set  in that section must match the password set in this
       file.

       The type set in that section must also match the type here - master  or
       slave.   In general, a master process is one running on the system with
       the UPS actually plugged into a serial port, and  a  slave  is  drawing
       power  from  the UPS but can't talk to it directly.  See the section on
       UPS types for more.

NOTIFY EVENTS

       upsmon senses several events as it monitors each UPS.  They are  called
       notify  events  as  they can be used to tell the users and admins about
       the change in status.  See the additional NOTIFY-related sections below
       for information on customizing the delivery of these messages.

       ONLINE The UPS is back on line.

       ONBATT The UPS is on battery.

       LOWBATT
              The UPS battery is low (as determined by the driver).

       FSD    The UPS has been commanded into the "forced shutdown" mode.

       COMMOK Communication with the UPS has been established.

       COMMBAD
              Communication with the UPS was just lost.

       SHUTDOWN
              The local system is being shut down.

       REPLBATT
              The UPS needs to have its battery replaced.

       NOCOMM The UPS can't be contacted for monitoring.

NOTIFY COMMAND

       In  upsmon.conf(5),  you  can  configure a program called the NOTIFYCMD
       that will handle events that occur.

            NOTIFYCMD "path to program"

            NOTIFYCMD "/usr/local/bin/notifyme"

       Remember to wrap the path in "quotes" if it contains any spaces.

       The program you run as your NOTIFYCMD can use the environment variables
       NOTIFYTYPE  and UPSNAME to know what has happened and on which UPS.  It
       also receives the notification message (see below) as  the  first  (and
       only) argument, so you can deliver a preformatted message too.

       Note  that the NOTIFYCMD will only be called for a given event when you
       set the EXEC flag by using the notify flags, below:

NOTIFY FLAGS

       By default, all notify events (see above)  generate  a  global  message
       (wall)  to  all  users,  plus  they are logged via the syslog.  You can
       change this with the NOTIFYFLAG directive in the configuration file:

            NOTIFYFLAG notifytype flags

            Examples:

            NOTIFYFLAG ONLINE SYSLOG

            NOTIFYFLAG ONBATT SYSLOG+WALL

            NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC

       The flags that can be set on a given notify event are:

       SYSLOG Write this message to the syslog.

       WALL   Send this message to all users on the system via 'wall'.

       EXEC   Execute the NOTIFYCMD.

       IGNORE Don't do anything.  If you use this, don't use any of the  other
              flags.

       You can mix these flags.  "SYSLOG+WALL+EXEC" does all three for a given
       event.

NOTIFY MESSAGES

       upsmon comes with default messages  for  each  of  the  NOTIFY  events.
       These can be changed with the NOTIFYMSG directive.

            NOTIFYMSG type "message"

            Examples:

            NOTIFYMSG ONLINE "UPS %s is getting line power"

            NOTIFYMSG ONBATT "Someone pulled the plug on %s"

       The  first  instance  of  %s is replaced with the identifier of the UPS
       that generated the event.  These messages are used when  sending  walls
       to  the  users  directly  from  upsmon,  and  are  also  passed  to the
       NOTIFYCMD.

POWER VALUES

       The "current overall power value" is the sum  of  all  UPSes  that  are
       currently  able  to supply power to the system hosting upsmon.  Any UPS
       that is either on line or just on battery contributes to  this  number.
       If  a UPS is critical (on battery and low battery) or has been put into
       "forced shutdown" mode, it no longer contributes.

       A "power value" on a MONITOR line in the config file is the  number  of
       power supplies that the UPS runs on the current system.

            MONITOR upsname powervalue username password type

       Normally, you only have one power supply, so it will be set to 1.

            MONITOR myups@myhost 1 username mypassword master

       On  a large server with redundant power supplies, the power value for a
       UPS may be greater than 1.  You may also have more  than  one  of  them
       defined.

            MONITOR ups-alpha@myhost 2 username mypassword master

            MONITOR ups-beta@myhost 2 username mypassword master

       You  can  also set the power value for a UPS to 0 if it does not supply
       any power to that system.  This is generally used when you want to  use
       the  upsmon  notification  features  for  a  UPS  even  though it's not
       actually running the system that  hosts  upsmon.   Don't  set  this  to
       "master"  unless  you  really  want  to  power  this  UPS off when this
       instance of upsmon needs to shut down for its own reasons.

            MONITOR faraway@anotherbox 0 username mypassword slave

       The "minimum power value" is the number of power supplies that must  be
       receiving power in order to keep the computer running.

            MINSUPPLIES value

       Typical  PCs only have 1, so most users will leave this at the default.

            MINSUPPLIES 1

       If you have a server or similar system with redundant power, then  this
       value  will  usually  be  set  higher.   One  that requires three power
       supplies to be running at all times would simply set it to 3.

            MINSUPPLIES 3

       When the current overall power value  drops  below  the  minimum  power
       value,  upsmon starts the shutdown sequence.  This design allows you to
       lose some of your power  supplies  in  a  redundant  power  environment
       without  bringing  down  the entire system while still working properly
       for smaller systems.

UPS TYPES

       upsmon and upsd(8) don't always run on the same system.  When they  do,
       any  UPSes  that  are  directly  attached  to the upsmon host should be
       monitored in "master" mode.  This makes  upsmon  take  charge  of  that
       equipment,  and  it  will wait for slaves to disconnect before shutting
       down the local system.  This allows  the  distant  systems  (monitoring
       over  the  network) to shut down cleanly before upsdrvctl shutdown runs
       and turns them all off.

       When upsmon runs as a slave, it is relying on  the  distant  system  to
       tell  it  about  the state of the UPS.  When that UPS goes critical (on
       battery and low battery), it immediately  invokes  the  local  shutdown
       command.   This  needs to happen quickly.  Once it disconnects from the
       distant upsd(8) server, the master upsmon will start its  own  shutdown
       process.   Your  slaves  must all shut down before the master turns off
       the power or filesystem damage may result.

       upsmon deals with slaves that get wedged, hang, or  otherwise  fail  to
       disconnect  from  upsd(8)  in  a timely manner with the HOSTSYNC timer.
       During a shutdown situation, the master upsmon will give up after  this
       interval  and  it  will  shut  down anyway.  This keeps the master from
       sitting there forever (which would  endanger  that  host)  if  a  slave
       should break somehow.  This defaults to 15 seconds.

       If  your master system is shutting down too quickly, set the FINALDELAY
       interval to something greater than the default 15 seconds.   Don't  set
       this  too  high,  or  your  UPS battery may run out of power before the
       master upsmon process shuts down that system.

TIMED SHUTDOWNS

       For those rare situations where the shutdown process can't be completed
       between  the  time  that  low battery is signalled and the UPS actually
       powers off the load, use the upssched(8) helper program.  You  can  use
       it  along  with upsmon to schedule a shutdown based on the "on battery"
       event.  upssched can then come back to upsmon to initiate the  shutdown
       once it's run on battery too long.

       This can be complicated and messy, so stick to the default critical UPS
       handling if you can.

REDUNDANT POWER SUPPLIES

       If you have more than one power supply for  redundant  power,  you  may
       also  have  more than one UPS feeding your computer.  upsmon can handle
       this.  Be sure to set  the  UPS  power  values  appropriately  and  the
       MINSUPPLIES  value high enough so that it keeps running until it really
       does need to shut down.

       For example, the HP NetServer LH4  by  default  has  3  power  supplies
       installed, with one bay empty.  It has two power cords, one per side of
       the box.  This means that one power cord powers two power supply  bays,
       and that you can only have two UPSes supplying power.

       Connect  UPS  "alpha"  to  the cord feeding two power supplies, and UPS
       "beta" to the cord that feeds the third and  the  empty  slot.   Define
       alpha  as  a  powervalue  of 2, and beta as a powervalue of 1.  Set the
       MINSUPPLIES to 2.

       When alpha goes on battery, your current overall power value will  stay
       at  3,  as  it's still supplying power.  However, once it goes critical
       (on battery and low battery), it will stop contributing to the  current
       overall  power  value.   That  means  the value will be 1 (beta alone),
       which is less than 2.  That is insufficient  to  run  the  system,  and
       upsmon will invoke the shutdown sequence.

       However,  if beta goes critical, subtracting its contribution will take
       the current overall value from 3 to 2.  This is  just  high  enough  to
       satisfy the minimum, so the system will continue running as before.  If
       beta returns later, it will be re-added and the current value  will  go
       back  to  3.   This  allows  you  to  swap  out  UPSes,  change a power
       configuration, or whatever, as long as you maintain the  minimum  power
       value at all times.

MIXED OPERATIONS

       Besides  being  able to monitor multiple UPSes, upsmon can also monitor
       them as different roles.  If you have  a  system  with  multiple  power
       supplies  serviced  by  separate  UPS  batteries, it's possible to be a
       master on one and a slave on the other.  This usually happens when  you
       run  out  of serial ports and need to do the monitoring through another
       system nearby.

       This is also complicated, especially when it comes time to power down a
       UPS  that  has  gone critical but doesn't supply the local system.  You
       can do this with some scripting magic in your  notify  command  script,
       but it's beyond the scope of this manual.

FORCED SHUTDOWNS

       When upsmon is forced to bring down the local system, it sets the "FSD"
       (forced shutdown) flag on any UPSes that it is running in master  mode.
       This  is used to synchronize slaves in the event that a master UPS that
       is otherwise OK needs to be brought down due to some pressing event  on
       the master.

       You  can  manually  invoke  this  mode on the master upsmon by starting
       another copy with '-c fsd'.  This is useful when you want to initiate a
       shutdown before the critical stage through some external means, such as
       upssched(8).

DEAD UPSES

       In the event that upsmon can't reach  upsd(8),  it  declares  that  UPS
       "dead"   after   some   interval   controlled   by   DEADTIME   in  the
       upsmon.conf(5).  If this happens while that UPS was last known to be on
       battery,  it is assumed to have gone critical and no longer contributes
       to the overall power value.

       upsmon will alert you to a UPS that can't be contacted  for  monitoring
       with  a  "NOCOMM"  notifier  by default every 300 seconds.  This can be
       changed with the NOCOMMWARNTIME setting.

RELOADING NUANCES

       upsmon usually gives up root powers for the process that does  most  of
       the  work,  including  handling  signals  like  SIGHUP  to  reload  the
       configuration file.   This  means  your  upsmon.conf(8)  file  must  be
       readable by the non-root account that upsmon switches to.

       If  you  want  reloads  to  work, upsmon must run as some user that has
       permissions to read the configuration file.  I recommend making  a  new
       user  just  for  this  purpose, as making the file readable by "nobody"
       (the default user) would be a bad idea.

       See the RUN_AS_USER section in upsmon.conf(8) for more on this topic.

       Additionally,  you  can't  change  the  SHUTDOWNCMD  or   POWERDOWNFLAG
       definitions  with  a  reload  due  to  the split-process model.  If you
       change those values, you must stop upsmon and start it back up.  upsmon
       will  warn  you  in  the  syslog if you make changes to either of those
       values during a reload.

SIMULATING POWER FAILURES

       To test a synchronized  shutdown  without  pulling  the  plug  on  your
       UPS(es), you need only set the forced shutdown (FSD) flag on them.  You
       can do this by calling upsmon again to set the flag - i.e.:

            upsmon -c fsd

       After that, the master and the slaves  will  do  their  usual  shutdown
       sequence  as  if the battery had gone critical.  This is much easier on
       your UPS equipment, and it beats crawling under  a  desk  to  find  the
       plug.

FILES

       upsmon.conf(5)

SEE ALSO

   Server:
       upsd(8)

   Clients:
       upsc(8), upscmd(8), upsrw(8), upsmon(8)

   CGI programs:
       upsset.cgi(8), upsstats.cgi(8), upsimage.cgi(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/

                                Mon Jan 22 2007