NAME

       powercom - UPS driver for Powercom/Trust/Advice UPS equipment

NOTE

       This  man  page  only  documents  the hardware-specific features of the
       powercom  driver.   For  information  about  the   core   driver,   see
       nutupsdrv(8).

SUPPORTED HARDWARE

       This  driver  supports  many  similar  kinds of UPS hardware.  The most
       common ones are the Trust 425/625, Powercom,  and  Advice  Partner/King
       PR750.  Others using the same protocol may also work.

EXTRA ARGUMENTS

       This   driver   supports   the   following  optional  settings  in  the
       ups.conf(5):

       linevoltage=value
              An integer specifying  the  mains  voltage.  It  can't  be  auto
              detected.   Acceptable  values  are  in  the range of 110-120 or
              220-240. The default is 230.

       manufacturer=name
              Specify  the  manufacturer  name,  which  also  can't  be   auto
              detected.  This  is  a  user  defined  string  so  any  name  is
              acceptable. The default is PowerCom.

       modelname=name
              Specify the model name, which also can't be auto detected.  This
              is  a user defined string so any name is acceptable. The default
              is Unknown.

       serialnumber=value
              Like modelname above, but for the serial number. The default  is
              Unknown.

       type=name
              The exact type of the communication protocol within the powercom
              family, that will be used to communicate with the UPS. The  type
              is  named  after  the  first  modelname that was coded with that
              protocol. The acceptable names are KP625AP,  Trust,  Egys,  KIN,
              BNT,  IMP and BNT-other. The default is Trust.  BNT-other - it's
              a special type for BNT 100-120V models for this type you can  (I
              think  must!) specify voltage, batteryPercentage, loadPercentage
              and validationSequence.

       numOfBytesFromUPS=value
              The number of  bytes  in  a  UPS  frame.  The  default  is  type
              dependant and is given below.

       methodOfFlowControl=name
              The  method of serial communication flow control that is engaged
              by the UPS. The default is type dependant and  is  given  below.
              Acceptable names are dtr0rts1, dtr1 or no_flow_control.

       shutdownArguments={{minutes,seconds},whether_minutes_should_be_used}
              The  minutes  and  seconds  that  the  UPS  should  wait between
              receiving the shutdown command and actually  shutting  off.  The
              other  argument  should  be set to the character n only when the
              minutes value should be skipped and not sent  to  the  UPS.  The
              default  is  type  dependant  and is given below. The braces and
              commas are mandatory. Note that there should be no  white  space
              characters.

       voltage={coefficient1,coefficient2,coefficient3,coefficient4}
              Only  for  KP625AP,  Trust,  Egys, BNT-other A quad that is used
              convert the raw data to  human  readable  voltage  reading.  The
              default  is  type dependant and is given below. Do note that the
              braces and commas are mandatory, as well as the  lack  of  white
              space characters.

       frequency={coefficient1,coefficient2}
              Only  for KP625AP, Trust, Egys A pair to convert the raw data to
              human readable frequency reading. The default is type  dependant
              and  is  given  below.  Do  note  that the braces and commas are
              mandatory as well, as the lack of white space characters.

       batteryPercentage={coefficient1,coefficient2,coefficient3,coefficient4,coefficient5}
              Only for KP625AP, Trust, Egys, BNT-other A 5  tuple  to  convert
              the  raw  data to human readable battery percentage reading. The
              default is type dependant and is given below. Do note  that  the
              braces  and  commas  are  mandatory,  as the lack of white space
              characters.

       loadPercentage={coefficient1,coefficient2,coefficient3,coefficient4}
              Only for KP625AP, Trust, Egys, BNT-other A quad to  convert  the
              raw  data to human readable load percentage reading. The default
              is type dependant and is given below. Do note  that  the  braces
              and commas are mandatory, as the lack of white space characters.

       validationSequence={{index1,value1},{index2,value2},{index3,value3}}
              Only for KP625AP, Trust, Egys, BNT-other 3 pairs to be used  for
              validating  the  UPS  by  comparing  bytes  of the raw data with
              constant values. The default is  type  dependant  and  is  given
              below. The braces and commas are mandatory, as the lack of white
              space characters.

DEFAULT VALUES FOR THE EXTRA ARGUMENTS

       linevoltage = 230

       manufacturer = PowerCom

       modelname = Unknown

       serialnumber = Unknown

       type = Trust

       The rest of the  default  values  for  the  extra  arguments  are  type
       dependant:

       Trust

              numOfBytesFromUPS = 11

              methodOfFlowControl = dtr0rts1

              validationSequence = {{5,0},{7,0},{8,0}}

              shutdownArguments = {{0,10},n}

              frequency = {0.00020997,0.00020928}

              loadPercentage = {6.1343,-0.3808,4.3110,0.1811}

              batteryPercentage = {5.0000,0.3268,-825.00,4.5639,-835.82}

              voltage = {1.9216,-0.0977,0.9545,0.0000}

       KP625AP

              numOfBytesFromUPS = 16

              methodOfFlowControl = dtr0rts1

              validationSequence = {{5,0x80},{7,0},{8,0}}

              shutdownArguments = {{0,10},n}

              frequency = {0.00020997,0.00020928}

              loadPercentage = {6.1343,-0.3808,4.3110,0.1811}

              batteryPercentage = {5.0000,0.3268,-825.00,4.5639,-835.82}

              voltage = {1.9216,-0.0977,0.9545,0.0000}

       Egys

              numOfBytesFromUPS = 16

              methodOfFlowControl = no_flow_control

              validationSequence = {{5,0x80},{7,0},{8,0}}

              shutdownArguments = {{0,10},n}

              frequency = {0.00020997,0.00020928}

              loadPercentage = {6.1343,-0.3808,1.3333,0.6667}

              batteryPercentage = {5.0000,0.3268,-825.00,2.2105,-355.37}

              voltage = {1.9216,-0.0977,0.9545,0.0000}

       IMP

              numOfBytesFromUPS = 16

              methodOfFlowControl = no_flow_control

              validationSequence = {{5,0xFF},{7,0},{8,0}}

              shutdownArguments = {{1,30},y}

       KIN

              numOfBytesFromUPS = 16

              methodOfFlowControl = no_flow_control

              validationSequence = {{11,0x4b},{8,0},{8,0}}

              shutdownArguments = {{1,30},y}

       BNT

              numOfBytesFromUPS = 16

              methodOfFlowControl = no_flow_control

              validationSequence = {{11,0x42},{8,0},{8,0}}

              shutdownArguments = {{1,30},y}

       BNT-other

              numOfBytesFromUPS = 16

              methodOfFlowControl = no_flow_control

              validationSequence = {{8,0},{8,0},{8,0}}

              shutdownArguments = {{1,30},y}

              loadPercentage = {1.4474,0.0,0.8594,0.0}

              batteryPercentage = {5.0000,0.3268,-825.00,0.46511,0}

              voltage = {1.9216,-0.0977,0.82857,0.0000}

AUTHOR

       Peter Bieringer <pb@bieringer.de> Alexey Sidorov <alexsid@altlinux.org>

SEE ALSO

   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/